EasyManua.ls Logo

Siemens 7SJ82 - Information List

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
Dyn.s: Cold load PU
_:8131:33 Definite-T 1:Effect. b.
cold-load pickup
no
yes
no
_:8131:40 Definite-T 1:Stage
blocked
no
yes
no
_:8131:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:8131:34 Definite-T 1:Effected by
binary input
no
yes
no
_:8131:41 Definite-T 1:Stage
blocked
no
yes
no
_:8131:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:25 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:501 General:>Test of direction SPS I
_:2311:301 General:Test direction ACD O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:8131:81 Definite-T 1:>Block stage SPS I
_:8131:501 Definite-T 1:>Release delay & op. SPS I
_:8131:84 Definite-T 1:>Activ. dyn. settings SPS I
_:8131:500 Definite-T 1:>Block delay & op. SPS I
_:8131:54 Definite-T 1:Inactive SPS O
_:8131:52 Definite-T 1:Behavior ENS O
_:8131:53 Definite-T 1:Health ENS O
_:8131:60 Definite-T 1:Inrush blocks operate ACT O
_:8131:62 Definite-T 1:Dyn.set. AR cycle1act. SPS O
_:8131:63 Definite-T 1:Dyn.set. AR cycle2act. SPS O
_:8131:64 Definite-T 1:Dyn.set. AR cycle3act. SPS O
6.6.4.4
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
418 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals