Settings
Addr. Parameter C Setting Options Default Setting
Pulse detect.#
_:1 Pulse detect.#:Mode
off
on
test
off
_:2 Pulse detect.#:Operate &
flt.rec. blocked
no
yes
no
_:102 Pulse detect.#:V0>
threshold value
0.300 V to 200.000 V 30.000 V
_:101 Pulse detect.#:3I0>
threshold value
1 A @ 100 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.000 A
_:103 Pulse detect.#:3I0 delta
pulse off-on
5 % to 50 % 10 %
_:104 Pulse detect.#:Pulse-on
duration
0.20 s to 10.00 s 1.00 s
_:105 Pulse detect.#:Pulse-off
duration
0.20 s to 10.00 s 1.50 s
_:109 Pulse
detect.#:Max.tolera.puls
e-on or off
0.02 s to 2.00 s 0.15 s
_:107 Pulse detect.#:No. of
pulses for operate
2 to 100 3
_:108 Pulse detect.#:Moni-
toring time(in pulses)
2 to 100 5
Information List
No.
Information Data Class
(Type)
Type
Pulse detect.#
_:81 Pulse detect.#:>Block stage SPS I
_:54 Pulse detect.#:Inactive SPS O
_:52 Pulse detect.#:Behavior ENS O
_:53 Pulse detect.#:Health ENS O
_:302 Pulse detect.#:Detected pulses MV O
_:55 Pulse detect.#:Pickup ACD O
_:56 Pulse detect.#:Operate delay expired ACT O
_:57 Pulse detect.#:Operate ACT O
6.15.13.3
6.15.13.4
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 627
C53000-G5040-C017-8, Edition 07.2017