Overvoltage Protection with Zero-Sequence Voltage/Residual
Voltage
Overview of Functions
The Overvoltage protection with zero-sequence voltage/residual voltage function (ANSI 59N):
Detects ground faults in isolated or arc-suppression-coil-grounded systems
Determines the phase affected by the ground fault
Works with electrical machines to detect ground faults in the stator winding
Structure of the Function
The Overvoltage protection with zero-sequence voltage/residual voltage function is used in protection
function groups with voltage measurement.
The Overvoltage protection with zero-sequence voltage/residual voltage function comes factory-set with
1 stage. A maximum of 3 stages can be operated simultaneously in the function.
The stages have an identical structure.
[dwu0ovps-030211-01.tif, 2, en_US]
Figure 6-183 Structure/Embedding of the Function
6.24
6.24.1
6.24.2
Protection and Automation Functions
6.24 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage
704 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017