Protection Stage
Description
Logic of the Stage Vdiff>
[Lo_voltdiffstage_20140715, 2, en_US]
Figure 7-43
Logic of the Protection Stage Vdiff>
Measurand, Pickup and Operate
In the protection stage, the differential-voltage value is converted to a p.u. value in relation to the capacitor-
bank reference voltage.
If the converted value exceeds the Threshold value, a
Pickup
indication is issued. If the threshold is
exceeded continuously during the operate delay, an
Operate
signal is issued.
7.7.4
7.7.4.1
Capacitor Bank Protection
7.7 Voltage Differential Protection for Capacitors
1040 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017