Addr. Parameter C Setting Options Default Setting
Trip logic
_:5341:103 Trip logic:Reset of
trip command
with I<
with I< & aux.contact
with dropout
with I<
Circuit break.
_:4261:101 Circuit
break.:Output time
0.02 s to 1800.00 s 0.10 s
_:4261:105 Circuit
break.:Indicat. of
breaking values
with trip
always
always
Manual close
_:6541:101 Manual
close:Action time
0.01 s to 60.00 s 0.30 s
_:6541:102 Manual close:CB
open dropout delay
0.00 s to 60.00 s 0.00 s
Control
_:4201:101 Control:Control
model
status only
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
SBO w. enh.
security
_:4201:102 Control:SBO time-
out
0.01 s to 1800.00 s 30.00 s
_:4201:103 Control:Feedback
monitoring time
0.01 s to 1800.00 s 1.00 s
_:4201:104 Control:Check
switching authority
no
yes
advanced
yes
_:4201:105 Control:Check if
pos. is reached
no
yes
yes
_:4201:106 Control:Check
double activat. blk.
no
yes
yes
_:4201:107 Control:Check blk.
by protection
no
yes
yes
Switching authority
_:4201:151 Control:Swi.dev.
related sw.auth.
0
1
false
_:4201:152 Control:Specific sw.
authorities
0
1
true
_:4201:115 Control:Specific
sw.auth. valid for
station
station/remote
remote
station/remote
_:4201:153 Control:Num. of
specific sw.auth.
2 to 5 2
_:4201:155 Control:Ident.
sw.auth. 1
Freely editable text
_:4201:156 Control:Ident.
sw.auth. 2
Freely editable text
_:4201:157 Control:Ident.
sw.auth. 3
Freely editable text
_:4201:158 Control:Ident.
sw.auth. 4
Freely editable text
Control Functions
8.2 Switching Devices
1092 SIPROTEC 5, Overcurrent Protection, Manual