Figure 8-40
Feeder Bay for a Double Busbar System
The CFC chart that is required to implement the interlocking equation is shown in the next figure.
[scverpla-270511-01.tif, 1, en_US]
Figure 8-41 Interlocking Chart for Bay Interlocking
Since the Disconnector function block provides the defined position On or Off, the exclusive OR gate XOR is
not necessary for interlocking. A simple OR suffices.
Control Functions
8.3 Control Functionality