This applies to automatic reclosing as well. Switching commands must be prevented as long as automatic
reclosing is active.
The default setting for blocking by the protection function is therefore yes. If necessary, you can disable this
blocking. You can find the settings on the same page as the double-activation blocking (see Figure 8-44).
i
i
NOTE
Remember, for instance, that pickup of the thermal overload protection can create a fault as well and thus
prevent switching commands.
i
i
NOTE
Note that the command check Blocking by protection function is only available for controlling circuit
breakers, because in this case a unique relationship with protection functions and automatic reclosing has
been configured. In disconnectors, this relationship is not always unique, precisely with regard to the 1 1/2
circuit-breaker layout, and it must be mapped for each system using CFC charts.
To carry out the command check Blocking by protection function for disconnectors, use the following
indications (if present) in your interlocking conditions:
Group indication: Pickup (Function group Line)
Circuit-breaker failure protection: Pickup (Circuit-breaker failure protection)
General: In progress (Automatic reclosing function)
Command Logging
All commands in the sequence are logged. The command log contains:
Date and time
Name of the switching device (or function group)
Reason for the transmission (SEL = Selected, OPR = Operate, CMT = Command execution end, SPN =
Spontaneous)
Status or switching direction
EXAMPLE
The following example illustrates control of a disconnector QB1 for various cases.
Successful command output
Interrupted command
Command interrupted by switchgear interlocking
Command ended due to missing feedback
Spontaneous change of switch position without command output
Figure 8-46 to Figure 8-52 indicates command logging for various scenarios of the standard control model
SBO with feedback monitoring.
8.3.2
Control Functions
8.3 Control Functionality
SIPROTEC 5, Overcurrent Protection, Manual 1121
C53000-G5040-C017-8, Edition 07.2017