Initialization and Configuration of the Protection Interface in DIGSI 5
If the device is provided with modules, proceed as follows:
Select the desired communication module in the rear view of the device.
Use the Communication protocols text box to select the protection interface. A text box entitled Protec-
tion interface will then appear.
[scconfcp-241110-01.tif, 1, en_US]
Figure 3-51 Selection of the Communication Protocol
Then select the Select constellation text box to select the number of devices (see next figure).
[scconfws-241110-01.tif, 1, en_US]
Figure 3-52 Selecting the Constellation
i
i
NOTE
You have the option of changing the number of devices (for example 2 protection communication
devices) depending on the product code any way you like via the Select constellation text box.
If you change the number of devices via the Select constellation text box, all activated constellation
settings are lost.
3.5.3.4
System Functions
3.5 Protection Communication
122 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017