Parameter (End Supervision Group): Binary input
Default setting (_:109) Binary input = 1
Parameter Binary input is used to define the highest binary input for the last I/O module (see (_:108)
I/O module ID) that you want to assign to a supervision group.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 Superv.Grp.#:Mode
off
on
test
on
Superv. signal
_:104 Superv.Grp.#:I/O module
ID
I/O module 1
I/O module 2
I/O module 3
I/O module 4
I/O module 5
I/O module 6
I/O module 7
I/O module 8
I/O module 9
I/O module 10
I/O module 11
I/O module 12
I/O module 13
I/O module 14
I/O module 15
I/O module 1
_:105 Superv.Grp.#:Binary
input
1 to 256 1
_:102 Superv.Grp.#:Enable
variable group
0
1
false
Supervis. grp. start
_:106 Superv.Grp.#:I/O module
ID
I/O module 1
I/O module 2
I/O module 3
I/O module 4
I/O module 5
I/O module 6
I/O module 7
I/O module 8
I/O module 9
I/O module 10
I/O module 11
I/O module 12
I/O module 13
I/O module 14
I/O module 15
I/O module 1
_:107 Superv.Grp.#:Binary
input
1 to 256 1
9.3.3.5
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual 1255
C53000-G5040-C017-8, Edition 07.2017