Addr. Parameter C Setting Options Default Setting
_:6 Supv. sum I:Delay super-
vision alarm
0.00 s to 100.00 s 5.00 s
Information List
No. Information Data Class
(Type)
Type
Supv. sum I
_:82 Supv. sum I:>Block function SPS I
_:54 Supv. sum I:Inactive SPS O
_:52 Supv. sum I:Behavior ENS O
_:53 Supv. sum I:Health ENS O
_:71 Supv. sum I:Failure SPS O
Current Phase-Rotation Supervision
Overview of Functions
The Current phase-rotation supervision function monitors the phase sequence of the secondary-circuit
currents by monitoring the sequence of the zero crossings (with same sign) of the currents. This enables the
device to detect connections that were inverted during commissioning. The criterion for the check is the
setting of the Phase sequence parameter.
The current measurement is based on the RMS values of the fundamental component.
Structure of the Function
The Current phase-rotation supervision function is located in the Power-system data of each 3-phase
current measurement point.
[dwstrcrs-040211-01.tif, 3, en_US]
Figure 9-30 Structure/Embedding of the Function
9.3.11.6
9.3.12
9.3.12.1
9.3.12.2
Supervision Functions
9.3 Supervision of the Secondary System
SIPROTEC 5, Overcurrent Protection, Manual 1279
C53000-G5040-C017-8, Edition 07.2017