EasyManua.ls Logo

Siemens 7SJ85 - Measuring Transducers; Overview of Functions; Structure of the Function; Function Description

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Measuring Transducers
Overview of Functions
Measuring transducers with an input rated at 20 mA can be used in the devices. 4 such inputs are available as
module ANAI-CA-4EL, which can be plugged into a communication module slot (for instance, port E or F). Up
to 4 such modules can be plugged in. Typically, slowly changing process variable such as temperature or gas
pressure are recorded with such 20-mA measured values and reported to the substation automation tech-
nology.
Structure of the Function
The measuring-transducer blocks are embedded in the Analog units function group and contain input and
output channels that are configurable independently of each other.
[dwstrumu-050313-01.tif, 1, en_US]
Figure 10-24 Structure/Embedding of the Function
Function Description
The 20-mA inputs typically transmit a value which represents a physical quantity such as a temperature or a
pressure. Therefore, the device must contain a characteristic curve that assigns the physical quantity to the
20-mA value. If the parameter Range active is not activated (no x in the check box), the function operates
over the range -24 mA to +24 mA. The setting of the range for the scaled value goes from a usable range of
-20 mA to +20 mA. The following figure shows an example.
10.10
10.10.1
10.10.2
10.10.3
Measured Values, Energy Values, and Supervision of the Primary System
10.10 Measuring Transducers
1346 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals