Tolerances
Currents 3I0 via protection-class current transformers:
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A)
3I0 via sensitive current transformer:
1 % of the setting value or 0.1 mA (I
rated
= 1.6 A)
or 0.5 mA (I
rated
= 8 A)
Times 1 % of the setting value or ± 10 ms
Technical Data
12.17 Directional Intermittent Ground-Fault Protection
SIPROTEC 5, Overcurrent Protection, Manual 1475
C53000-G5040-C017-8, Edition 07.2017