Siemens 7SJ85 - Pulse-Pattern Detection Stage

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pickup delay 0.00 s to 60.00 s Increments of 0.01 s
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 32 ms + OOT
103
at 50 Hz
Approx. 29 ms + OOT at 60 Hz
Extension of operate time during operation with
transformer inrush-current detection
Approx. 10 ms
Dropout time Approx. 32 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz
Current Operating Range
Minimum 3I0 threshold
for Y0 calculation
Protection-class current
transformers
30 mA sec. (I
rated
= 1 A)
150 mA sec. (I
rated
= 5 A)
Sensitive current trans-
former
1 mA sec. (I
rated
= 1 A)
5 mA sec. (I
rated
= 5 A)
Tolerances
Admittance
1 % of the setting value or 0.05 mS (I
rated
= 1.6 A) or
0.25 mS (I
rated
= 8 A), (f
rated
± 10 %)
Pulse-Pattern Detection Stage
Setting Values
V0> threshold value
0.300 V to
200.000 V
Increments of 0.001 V
3I0> threshold
value
Protection-class
current trans-
formers
For I
ph-rated
= 1 A 0.030 A to
35.000 A
Increments of 0.001 A
For I
ph-rated
= 5 A 0.15 A to 175.00 A Increments of 0.01 A
For I
N
transformer
type sensitive and
I
N-rated
= 1 A
For I
ph-rated
= 1 A 0.001 A to
35.000 A
Increments of 0.001 A
For I
ph-rated
= 5 A 0.001 A to
175.000 A
Increments of 0.001 A
For I
N
transformer
type sensitive and
I
N-rated
= 5 A
For I
ph-rated
= 1 A 0.005 A to
35.000 A
Increments of 0.001 A
For I
ph-rated
= 5 A 0.005 A to
175.000 A
Increments of 0.001 A
12.18.10
103
OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.18 Sensitive Ground-Fault Detection
1484 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017