EasyManua.ls Logo

Siemens 7SJ85 - Overvoltage Protection with Positive-Sequence Voltage

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overvoltage Protection with Positive-Sequence Voltage
Setting Values
Pickup value 0.300 V to 200.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 0.90 to 0.99 Increments of 0.01
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 25 ms + OOT
122
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays 1 % of the setting value or 10 ms
12.31
122
OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Technical Data
12.31 Overvoltage Protection with Positive-Sequence Voltage
SIPROTEC 5, Overcurrent Protection, Manual 1511
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals