Undervoltage Protection with Any Voltage
Setting Values
Measured value Measured phase-to-ground voltage V
A
Measured phase-to-ground voltage V
B
Measured phase-to-ground voltage V
C
Measured phase-to-phase voltage V
AB
Measured phase-to-phase voltage V
BC
Measured phase-to-phase voltage V
CA
Calculated phase-to-phase voltage V
AB
Calculated phase-to-phase voltage V
BC
Calculated phase-to-phase voltage V
CA
Calculated voltage V0
Method of measurement Fundamental component
RMS value
Threshold value
131
0.300 V to 340.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 25 ms + OOT
132
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Inactive, maintained;
Dropout of the pickup induced by blocking or by increasing the
measurand beyond the dropout threshold
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays 1 % of the setting value or 10 ms
12.38
131
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
132
OOT (Output Operating Time): additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Technical Data
12.38 Undervoltage Protection with Any Voltage
1522 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017