Figure A-35
Connection to V-Connected Voltage Transformer (Measurement of 2 Phase-to-Phase Voltages)
and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer (for example,
for Synchrocheck Applications)
[tvvolta7SJ82-260313-01.vsd, 1, en_US]
Figure A-36 Connection to a 1-Pole Insulated Voltage Transformer (Phase-to-Ground Voltage)
Appendix
A.9 Connection Examples of Voltage Transformers for Non-Modular Devices