Enter the confirmation ID.
•
Confirm the process with the softkey marked OK in the display.
After entering the confirmation ID, the acquisition blocking function is switched on.
[scerfass-310816-01, 1, en_US]
Figure 3-83 Activating the Acquisition Blocking
Manual updating of the switching device is possible from within the same menu.
•
Select Manual update (Figure 3-84) using the navigation keys.
•
With the navigation keys, select the switching-device setting to be updated manually (for example, off,
Figure 3-85).
•
Confirm the process with the softkey marked OK in the display.
[scstatus-310816-01, 1, en_US]
Figure 3-84 Activating the Manual Update
[scstatu2-310816-01, 1, en_US]
Figure 3-85 Selecting Position
The manually updated position of the switching device will be displayed.
[scstatu3-310816-01, 1, en_US]
Figure 3-86 Position of the Switching Device
NOTE
For safety reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.
System Functions
3.8 Other Functions
SIPROTEC 5, Overcurrent Protection, Manual 165