Structure of the Function Group
The Capacitor bank function group always contains the following functionality:
Protected object/equipment data (function block General)
Operational measured values
Capacitor bank device status and blocking by discharging (function block General)
Process monitor
Global compensation (function block General)
Output logic of the function group
Reset LED group
This functionality is essential for the Capacitor bank function group, so it cannot be loaded or deleted.
You can load the protection functions and supervision functions required for your application in the Capacitor
bank function group. The functions are available from the Global DIGSI 5 Library. Functions that are not
needed can be deleted from the function group.
[Dwstrcap-20140619-01.vsd, 2, en_US]
Figure 5-14
Structure of the Capacitor Bank Function Group
The Capacitor bank function group has interfaces with the following parts:
Measuring points
Circuit-breaker function group
Interfaces with the Measuring Points
The Capacitor bank function group receives the required measured values via the interfaces with the meas-
uring points. If you are using an application template, the Capacitor bank function group is already connected
to the specific measuring points.
5.4.2
Function-Group Types
5.4 Function-Group Type Capacitor Bank
SIPROTEC 5, Overcurrent Protection, Manual 213
C53000-G5040-C017-8, Edition 07.2017