Addr. Parameter C Setting Options Default Setting
Dyn.set: AR cycle 2
_:30 User curve #:Effected by
AR cycle 2
no
yes
no
_:37 User curve #:Stage
blocked
no
yes
no
_:15 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by
AR cycle 3
no
yes
no
_:38 User curve #:Stage
blocked
no
yes
no
_:16 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by
AR cycle gr. 3
no
yes
no
_:39 User curve #:Stage
blocked
no
yes
no
_:17 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b.
cold-load pickup
no
yes
no
_:40 User curve #:Stage
blocked
no
yes
no
_:18 User curve #:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
SIPROTEC 5, Overcurrent Protection, Manual 401
C53000-G5040-C017-8, Edition 07.2017