Additional Time Delay (Advanced Stage)
With the parameter Additional time delay, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.
Blocking of the Stage (Basic and Advanced Stage)
The following blockings reset the picked up stage completely:
Externally or internally via the binary input signal >Block stage (see chapter 6.6.3.1 Description )
Measuring-voltage failure (see chapter 6.6.3.1 Description )
Via the functionality of the dynamic settings (only in the advanced function type, see subtitle Influ-
ence of other functions via dynamic settings and chapter 6.3.8.1 Description ).
Blocking of the Time Delay (Basic and Advanced Stage)
You can use the binary input signal >Block delay & op. to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and a fault record is opened.
Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter 6.3.7.1 Description .
Influence of Other Functions via Dynamic Settings (Advanced Stage)
If available in the device, the following functions can influence the overcurrent-protection stages:
Automatic reclosing
Cold-load pickup detection
Binary input signal
The influence of these functions via dynamic settings is described in chapter 6.3.8.1 Description .
Application and Setting Notes
Parameter: Directional mode
Default setting (_:8161:111) Directional mode = forward
You use the Directional mode parameter to define the directional mode of the stage.
Parameter Value
Description
forward
Select this setting if the stage is to work in a forward direction (in the direc-
tion of the line).
reverse
Select this setting if the stage is to work in a reverse direction (in the direc-
tion of the busbar).
Parameter: Method of measurement
Recommended setting value (_:8161:8) Method of measurement = fundamental comp.
With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. (standard method) or the calculated RMS value.
Parameter Value
Description
fundamental comp.
Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
6.6.5.2
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
422 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017