Logic of the Stage
[lo_stage_arcprotection, 1, en_US]
Figure 6-91
Logic Diagram of the Stage
TheArc protection function uses a locally connected optical arc sensor or an external trip initiation by other
devices in order to detect arcs.
i
i
NOTE
Install the arc sensors inside the switchgear in such a way that they are not hidden behind other system
components!
Shadowing of the arc sensors must be avoided!
i
i
NOTE
Once an optical sensor has detected an arc, you must replace the affected optical sensor!
Within the Arc protection function, you can use a fast current-flow criterion as an additional release criterion.
The parameters for the current-flow criterion can be found in the General block. For each stage, you can
select individually whether the current-flow criterion must be evaluated as well.
Protection and Automation Functions
6.10 Arc Protection
502 SIPROTEC 5, Overcurrent Protection, Manual