Application and Setting Notes
Setting Notes for the Protection Device in the Infeed
The Arc protection function operates with 1 stage.
Set the parameters of the stage as follows:
•
Parameter: Operating mode = current and light
•
Parameter: Sensor = line sensor
•
Parameter: External trip initiation = no
•
Parameter: Channel = Arc mod. 1 channel 1 (Stage 1) → Busbar compartment supervision (infeed,
feeder 1, feeder 2)
You can find more information about the settings of the parameters Threshold I> and Threshold 3I0>
in chapter 6.10.4 Application and Setting Notes – General Settings.