Stage Description
Logic
[LoIntnon, 1, en_US]
Figure 6-111
Logic of the Non-Directional Intermittent Ground-Fault Protection
Measured Value 3I0
The intermittent ground-fault current 3I0 can either be measured via the standard ground-current input IN or
via the sensitive ground-current input I
NS
. It can also be calculated from the sum of the 3-phase currents. The
current value and its setting range depend on the parameter Connection type of the measuring point I-3ph.
6.13.3
Protection and Automation Functions
6.13 Non-Directional Intermittent Ground-Fault Protection
544 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017