Addr. Parameter C Setting Options Default Setting
_:107 User charact.#:Imin
cooling
1 A @ 100 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 100 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 50 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 50 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 2.500 A
_:108 User charact.#:Cool-
down factor Tau
0.5 to 20.0 7.0
_:109 User charact.#:Storage
of thermal replica
•
no
•
yes
no
_:110 User charact.#:Imax
thermal
1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:111 User charact.#:Behav. at
I> Imax therm.
•
current limiting
•
freeze therm. rep.
current limiting
_:112 User charact.#:Operate
char. curve
Setting options depend on
configuration
1.1 p.u., 600 s
_:101 User charact.#:Curve
based on preload
0 % to 100 % 100 %
Information List
No.
Information Data Class
(Type)
Type
User charact.#
_:81 User charact.#:>Block stage SPS I
_:500 User charact.#:>Reset thermal replica SPS I
_:501 User charact.#:>Emergency start SPS I
_:54 User charact.#:Inactive SPS O
_:52 User charact.#:Behavior ENS O
_:53 User charact.#:Health ENS O
_:300 User charact.#:Current warning SPS O
_:301 User charact.#:Thermal warning SPS O
_:302 User charact.#:Block close SPS O
_:55 User charact.#:Pickup ACD O
_:303 User charact.#:Operate alarm only ACT O
_:57 User charact.#:Operate ACT O
_:304 User charact.#:Time until close MV O
_:305 User charact.#:Time until trip MV O
_:306 User charact.#:Overload phase A MV O
_:307 User charact.#:Overload phase B MV O
_:308 User charact.#:Overload phase C MV O
_:309 User charact.#:Overload maximum MV O
_:310 User charact.#:Equival. current phs A MV O
_:311 User charact.#:Equival. current phs B MV O
6.20.6
Protection and Automation Functions
6.20 Thermal Overload Protection, User-Defined Characteristic Curve
674 SIPROTEC 5, Overcurrent Protection, Manual