EasyManua.ls Logo

Siemens 7SJ85 - Rate of Frequency Change Protection; Overview of Functions; Structure of the Function; General Functions (Undervoltage Test, Df;Dt Calculation)

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rate of Frequency Change Protection
Overview of Functions
The function Rate of frequency change protection is used to:
Detect a frequency change quickly
Prevent the system from not secure states caused by unbalance between the generated and consumed
active power
Network decoupling
Load shedding
Structure of the Function
The function Rate of frequency change protection can be used in protection function groups containing a
3‑phase voltage measurement.
2 function block types are available:
df/dt rising
df/dt falling
The function Rate of frequency change protection is preconfigured by the manufacturer with 1 df/dt rising
stage and 1 df/dt falling stage. A maximum of 5 df/dt rising stages and 5 df/dt falling stages can operate simul-
taneously within the function. Both of the function block types are similar in structure.
Undervoltage check and df/dt calculation are general functionalities and take place on the function level. All
stages use these general functionalities.
[dwdfdt01-160113-01.tif, 1, en_US]
Figure 6-219 Structure/Embedding of the Function
General Functions (Undervoltage Test, df/dt Calculation)
Description
Logic
The following figure represents the logic of undervoltage check and df/dt calculation. It applies to all types of
stages.
6.35
6.35.1
6.35.2
6.35.3
6.35.3.1
Protection and Automation Functions
6.35 Rate of Frequency Change Protection
SIPROTEC 5, Overcurrent Protection, Manual 785
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals