Parameter: Tripping delay
Default setting (_:13621:6) Operate delay = 1.00 s
The Operate delay parameter is used to determine the time by which the stage is delayed after the
pickup. This time delay depends on the specific application. The default value is practical for the applica-
tion described in the previous chapter.
Settings
Addr. Parameter C Setting Options Default Setting
Definite-T 1
_:13621:1 Definite-T 1:Mode
off
on
test
off
_:13621:2 Definite-T 1:Operate &
flt.rec. blocked
no
yes
no
_:13621:3 Definite-T 1:Threshold 1.00 to 1.40 1.40
_:13621:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 1.00 s
Therm.charact.
_:13591:1 Therm.charact.:Mode
off
on
test
off
_:13591:2 Therm.charact.:Operate
& flt.rec. blocked
no
yes
no
_:13591:3 Therm.charact.:Threshol
d
1.00 to 1.20 1.10
_:13591:101 Therm.charact.:Warning
delay
0.00 s to 60.00 s 10.00 s
_:13591:102 Therm.charact.:Cooling
time therm.replica
0 s to 100 000 s 3600 s
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:322 General:V/f MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
df/dt falling1
_:13621:81 Definite-T 1:>Block stage SPS I
_:13621:54 Definite-T 1:Inactive SPS O
_:13621:52 Definite-T 1:Behavior ENS O
_:13621:53 Definite-T 1:Health ENS O
_:13621:55 Definite-T 1:Pickup ACD O
_:13621:56 Definite-T 1:Operate delay expired ACT O
_:13621:57 Definite-T 1:Operate ACT O
Therm.charact.
_:13591:81 Therm.charact.:>Block stage SPS I
_:13591:501 Therm.charact.:>Reset thermal replica SPS I
_:13591:54 Therm.charact.:Inactive SPS O
6.39.4.3
6.39.4.4
Protection and Automation Functions
6.39 Overexcitation Protection
SIPROTEC 5, Overcurrent Protection, Manual 825
C53000-G5040-C017-8, Edition 07.2017