EasyManua.ls Logo

Siemens 7SJ85 - Page 866

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following applies for the restraint current:
I
Rest,REF
= |I
gnd,A
| + |I
gnd,B
| + |I
gnd,C
| + |I
A
| + |I
B
| + |I
C
|
i
i
NOTE
If both 1-phase neutral point and 3-phase ground side are connected, only the 1-phase neutral point is
used by the restricted ground-fault protection. The 3-phase ground side is not considered.
Pickup
If the I
Diff,REF
calculated differential current exceeds the calculated current I
char.
(see Figure 6-264), pickup
occurs and the internal processing is enabled. The pickup is indicated.
Operate Curve
The operate curve represented in the following figure consists of 2 parts. In the right part of the characteristic
curve, you will find a case of an internal ground fault. Under ideal conditions, the angle between the two
residual currents (∠(
I
0
*, I
0
**)) equals 0. With current-transformer saturation, angle errors can result. The right
part of the characteristic curve is valid for angles ≤ 90°. The tripping current is the current flowing at the
neutral point (
I
0
*). It is compared to the set or increased threshold value.
[dwausken-170712-01.tif, 1, en_US]
Figure 6-268 Operate Curve Depending on the Phase Angle between l
0
* and I
0
** at |I
0
*| = |I
0
**| (180° =
External Fault)
In case of an external ground fault, the zero-sequence current calculated from the phase currents reverses by
180°. The phase angle between the residual currents thus (∠(I
0
*, I
0
**)) equals 180°. They are located in the
left part of the operate curve and recognize a clearly increased pickup value. Angle deviations of 180° are
caused by transformer saturation in conjunction with external short-circuits.
The current I
Angle,REF
for the Angle Decision is determined from the following subtraction and summation:
I
Angle,REF
= |
I
0
* - I
0
**| - |I
0
* + I
0
**|
The resulting current I
Angle,REF
results from the respective fault conditions, which are illustrated in the following
figure. With an internal fault (angle = 0°), a current results that has a negative sign. If angle errors occur, the
sign remains negative. The amount of the current decreases.
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
866 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals