Addr. Parameter C Setting Options Default Setting
_:11101:1 Point 1:Mode
off
on
test
off
_:11101:40 Point 1:Threshold stage 1 -50°C to 250°C 100°C
_:11101:41 Point 1:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11101:42 Point 1:Threshold stage 2 -50°C to 250°C 120°C
_:11101:43 Point 1:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11101:44 Point 1:Sensor Setting options depend on config-
uration
Point 2
_:11102:46 Point 2:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11102:1 Point 2:Mode
off
on
test
off
_:11102:40 Point 2:Threshold stage 1 -50°C to 250°C 100°C
_:11102:41 Point 2:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11102:42 Point 2:Threshold stage 2 -50°C to 250°C 120°C
_:11102:43 Point 2:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11102:44 Point 2:Sensor Setting options depend on config-
uration
Point 3
_:11103:46 Point 3:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11103:1 Point 3:Mode
off
on
test
off
_:11103:40 Point 3:Threshold stage 1 -50°C to 250°C 100°C
_:11103:41 Point 3:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11103:42 Point 3:Threshold stage 2 -50°C to 250°C 120°C
_:11103:43 Point 3:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11103:44 Point 3:Sensor Setting options depend on config-
uration
Point 4
_:11104:46 Point 4:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
Protection and Automation Functions
6.47 Temperature Supervision
944 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017