Parameter Value Description
RLC rated current
Select this setting if you want to use the individual rated current of the RLC
object to be proteced (for example, a resistor or reactor) as the reference
value.
Parameter: RLC rated current
Default setting (_:2311:102) RLC rated current = 1000 A
With the parameter RLC rated current, you set the primary rated current of the respective protected
object which is usually a reactor or resistor branch within the capacitor-bank installation.
Capacitor Bank Protection
7.2 Overcurrent Protection for Capacitor Banks
972 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017