EasyManua.ls Logo

Siemens 7SJ85 - Page 981

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In this case, normalization with current I
c
will no longer work properly either. The normalization is canceled in
a phase-segregated manner. This means that the non-normalized value is used in place of the normalized
value (see Figure 7-8).
Charging/Energizing the Capacitor Bank or a Phase of the Bank
Charging of the bank takes place when the discharged bank is switched on to the network. Charging of a
phase can occur in case of network faults. If a phase-to-ground voltage drops to 0 V due to a network fault,
the respective phase is discharged and the return of the phase-to-ground (after the fault has been cleared) will
charge the phase.
Charging the bank or a phase of the bank causes inrush currents in the respective phases. To avoid overfunc-
tion in case of sensitive threshold settings, the stages using compensated unbalanced values are blocked in a
phase-selective way by setting
I
unbal.,comp.
to 0 A. These stages are:
Counter stage
I> stage, if set to operate with compensated unbalanced values
The blocking (
I
unbal.,comp.
set to 0 A) lasts for 250 ms after energizing detection. Afterwards, the calculated
I
unbal.,comp.
is processed again.
Energizing detection takes place in a phase-selective way by monitoring the phase current I
c
flowing into the
bank. If a phase current exceeds the threshold Current Thresh.CB Open, energizing in this phase is
detected.
Logic for Counting Faulty C-Elements
This part of the General functionality is only important if counter stages are used.
Capacitor Bank Protection
7.4 Current-Unbalance Protection for Capacitors, 3-Phase
SIPROTEC 5, Overcurrent Protection, Manual 981
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals