Introduction
1.3 Characteristics
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
25
Load Step Function
Detection of mechanical or thermal overload of the rotor.
Frequency Protection 81 O/U
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are inde-
pendently adjustable
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold.
Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has full memory capability)
True r.m.s. calculation
Adjustable thermal warning element
Adjustable alarm level based on current magnitude
Additional time constant setting for motors to accommodate the motor at standstill
Integration of the ambient temperature or coolant temperature is possible via internal temperature detection
or an external thermobox.
Monitoring Functions
Increased reliability due to monitoring of the internal measurement circuits as well as the hardware and soft-
ware
Fuse failure monitor with protection function blocking
Monitoring of the current transformer and voltage transformer secondary circuits using sum and symmetry
supervision with optional protection function blocking
Trip circuit monitoring possible
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s), 67N(s), 59N/64
Displacement voltage is measured or calculated from the three phase voltages.
Determination of a faulty phase on ungrounded or grounded systems.
Two-element ground fault detection: High-current element 50Ns-2 and overcurrent element 50Ns-1.
High sensitivity (as low as 1 mA)
Overcurrent element with definite time or inverse time delay.
For inverse-time overcurrent protection, a user-defined characteristic is available.
Direction determination with zero sequence quantities(I0, V0), wattmetric ground fault direction determina-
tion.
A sector characteristic can be set as directional characteristic
Any Element can be set as directional or non-directional — forward sensing directional, or reverse sensing
directional
Optionally applicable as additional ground fault protection.