Functions
2.17 Temperature Detection via RTD Box
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
253
9081A RTD 8 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 8: Type
9082A RTD 8 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 -50 .. 250 °C; 100 °C RTD 8: Temperature Stage 1
Pickup
9084 RTD 8 STAGE 1 -58 .. 482 °F; 212 °F RTD 8: Temperature Stage 1
Pickup
9085 RTD 8 STAGE 2 -50 .. 250 °C; 120 °C RTD 8: Temperature Stage 2
Pickup
9086 RTD 8 STAGE 2 -58 .. 482 °F; 248 °F RTD 8: Temperature Stage 2
Pickup
9091A RTD 9 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 9: Type
9092A RTD 9 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1 -50 .. 250 °C; 100 °C RTD 9: Temperature Stage 1
Pickup
9094 RTD 9 STAGE 1 -58 .. 482 °F; 212 °F RTD 9: Temperature Stage 1
Pickup
9095 RTD 9 STAGE 2 -50 .. 250 °C; 120 °C RTD 9: Temperature Stage 2
Pickup
9096 RTD 9 STAGE 2 -58 .. 482 °F; 248 °F RTD 9: Temperature Stage 2
Pickup
9101A RTD10 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD10: Type
9102A RTD10 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1 -50 .. 250 °C; 100 °C RTD10: Temperature Stage 1
Pickup
9104 RTD10 STAGE 1 -58 .. 482 °F; 212 °F RTD10: Temperature Stage 1
Pickup
9105 RTD10 STAGE 2 -50 .. 250 °C; 120 °C RTD10: Temperature Stage 2
Pickup
Addr. Parameter Setting Options Default Setting Comments