Introduction
1.3 Characteristics
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
26
Intermittent Ground Fault Protection
Detects and accumulates intermittent ground faults
Tripping after configurable total time.
Directional intermittent ground fault protection
Detects intermittent ground faults
Direction determination
Tripping after settable number of intermittent restrikes
Breaker Failure Protection 50 BF
By checking the current and/or evaluating the circuit breaker auxiliary contacts
Started by any integrated protection function that trips
Initiation possible via a binary input from an external protective device.
Flexible Protective Functions
Up to 20 customizable protection functions with three-phase or single-phase operation
Any calculated or directly measured quantity can be evaluated on principle.
Standard protection logic with a constant (i.e. definite-time) characteristic curve
Internal and configurable pickup and dropout delay
Modifiable message texts.
RTD box/temperature detection
Detection of any ambient temperatures or coolant temperatures using external RTD boxes or internal tem-
perature detection via the extension module I/O 2.
Phase Rotation
Selectable ABC or ACB by setting (static) or binary input (dynamic).
Circuit-Breaker Maintenance
Statistical methods to help adjust maintenance intervals for CB contacts according to their actual wear
Several independent subfunctions have been implemented (ΣI procedure, ΣI
x
procedure, 2P procedure and
I
2
t procedure)
Acquisition and conditioning of measured values for all subfunctions operates phase-selective using one
procedure-specific threshold per subfunction.