Technical Data
4.2 Definite-time Overcurrent Protection
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
361
Tolerances
Influencing Variables for Pickup and Dropout
Pickup times 3 % of setting value or 15 mA at I
Nom
= 1 A
or 75 mA at I
Nom
= 5 A
Time delays T 1 % or 10 ms
Auxiliary DC voltage in range 0.8 ≤ V
Aux
/V
AuxNom
≤ 1.15 1 %
Temperature in range –5 °C (41 °F) ≤ Θ
amb
≤ 55 °C (131 °F) 0.5 %/10 K
Frequency in the range of 25 Hz – 70 Hz
Frequency in the range of 0.95 ≤ f/f
Nom
≤ 1.05 (f
Nom
= 50 Hz
or 60 Hz)
1%
Frequency outside range 0.95 ≤ f/f
Nom
≤ 1.05 Increased tolerances
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
at instantaneous value of 50-3/50N-3 elements
1%
1%
Increased tolerances
Transient overreaction for τ > 100 ms (with full displace-
ment)
<5 %