322A Corr.factor IL3 P.System Data 1 0.9000 .. 1.1000 1.0000 Correction factor for magnitude
IL3
323A Corr.factor IE P.System Data 1 0.9000 .. 1.1000 1.0000 Correction factor for magnitude
IE
324A Corr.factor IEE P.System Data 1 0.9000 .. 1.1000 1.0000 Correction factor for magnitude
IEE
330 V-LPVT SEC P.System Data 1 3.00 .. 17.00 V 3.25 V rated secondary voltage LPVT
332A V-LPVT PHA P.System Data 1 -10.00 .. 10.00 ° 0.00 ° phase angle LPVT
401 WAVEFORMTRIGGER Osc. Fault Rec. Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform
Capture Record
404 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to
Trigger
405 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
406 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input
610 FltDisp.LED/LCD Device, General Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
611 Spont. FltDisp. Device, General YES
NO
NO Spontaneous display of flt.an-
nunciations
613A Gnd O/Cprot. w. P.System Data 1 Ignd (measured)
3I0 (calcul.)
Ignd (measured) Ground Overcurrent protection
with
614A OP. QUANTITY 59 P.System Data 1 Vphph
Vph-n
V1
V2
Vphph Opera. Quantity for 59 Overvolt.
Prot.
615A OP. QUANTITY 27 P.System Data 1 V1
Vphph
Vph-n
V1 Opera. Quantity for 27 Undervolt.
Prot.
640 Start image DD Device, General image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default Display
651 ParEN100(LC)blk Device, General OFF
ON
OFF DIGSI-config. over EN100 (LC)
blocked
660 IP adr[0](Prim) Device, General 0 .. 255 0 IP address [0] (NTP-Primary)
661 IP adr[1](Prim) Device, General 0 .. 255 0 IP address [1] (NTP-Primary)
662 IP adr[2](Prim) Device, General 0 .. 255 0 IP address [2] (NTP-Primary)
663 IP adr[3](Prim) Device, General 0 .. 255 0 IP address [3] (NTP-Primary)
664 IP adr[0] (Sec) Device, General 0 .. 255 0 IP address [0] (NTP-Sekundary)
665 IP adr[1] (Sec) Device, General 0 .. 255 0 IP address [1] (NTP-Sekundary)
666 IP adr[2] (Sec) Device, General 0 .. 255 0 IP address [2] (NTP-Sekundary)
667 IP adr[3] (Sec) Device, General 0 .. 255 0 IP address [3] (NTP-Sekundary)
668 Client activ Device, General OFF
ON
OFF Client activ
669 Daylight Set Device, General OFF
ON
OFF Daylight Set
670 Offset TZ/min Device, General -1440 .. 1440 min 60 min Offset for time zone in minutes
671 Offset DayT/min Device, General -1440 .. 1440 min 60 min Offset for daylight in minutes
672 W2S month Device, General 1 .. 12 3 month of time set winter to
summer
673 W2S week Device, General 1 .. 5 5 week of time set winter to
summer
674 W2S day Device, General Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Sunday day of time set winter to summer
675 W2S hour Device, General 1 .. 24 2 hour of time set winter to summer