Appendix
A.8 Settings
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
458
676 S2W month Device, General 1 .. 12 10 month of time set summer to
winter
677 S2W week Device, General 1 .. 5 5 week of time set summer to
winter
678 S2W day Device, General Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Sunday day of time set summer to winter
679 S2W hour Device, General 1 .. 24 3 hour of time set summer to winter
700 GOOSE-Stop Device, General YES
NO
NO GOOSE-Stop
1101 FullScaleVolt. P.System Data 2 0.10 .. 800.00 kV 20.00 kV Measurem:FullScaleVolt-
age(Equipm.rating)
1102 FullScaleCurr. P.System Data 2 10 .. 50000 A 400 A Measurem:FullScaleCur-
rent(Equipm.rating)
1107 I MOTOR START P.System Data 2 1A 0.40 .. 10.00 A 2.50 A Motor Start Current (Block 49,
Start 48)
5A 2.00 .. 50.00 A 12.50 A
1108 P,Q sign P.System Data 2 not reversed
reversed
not reversed P,Q operational measured values
sign
1201 FCT 50/51 50/51 Overcur. ON
OFF
ON 50, 51 Phase Time Overcurrent
1202 50-2 PICKUP 50/51 Overcur. 1A 0.10 .. 35.00 A; ∞ 4.00 A 50-2 Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
1203 50-2 DELAY 50/51 Overcur. 0.00 .. 60.00 sec; ∞ 0.00 sec 50-2 Time Delay
1204 50-1 PICKUP 50/51 Overcur. 1A 0.10 .. 35.00 A; ∞ 1.00 A 50-1 Pickup
5A 0.50 .. 175.00 A; ∞ 5.00 A
1205 50-1 DELAY 50/51 Overcur. 0.00 .. 60.00 sec; ∞ 0.50 sec 50-1 Time Delay
1207 51 PICKUP 50/51 Overcur. 1A 0.10 .. 4.00 A 1.00 A 51 Pickup
5A 0.50 .. 20.00 A 5.00 A
1208 51 TIME DIAL 50/51 Overcur. 0.05 .. 3.20 sec; ∞ 0.50 sec 51 Time Dial
1209 51 TIME DIAL 50/51 Overcur. 0.50 .. 15.00 ; ∞ 5.00 51 Time Dial
1210 51 Drop-out 50/51 Overcur. Instantaneous
Disk Emulation
Disk Emulation Drop-out characteristic
1211 51 IEC CURVE 50/51 Overcur. Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
1212 51 ANSI CURVE 50/51 Overcur. Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
1213A MANUAL CLOSE 50/51 Overcur. 50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
50-2 instant. Manual Close Mode
1214A 50-2 active 50/51 Overcur. Always Always 50-2 active
1215A 50 T DROP-OUT 50/51 Overcur. 0.00 .. 60.00 sec 0.00 sec 50 Drop-Out Time Delay
1216A 50-3 active 50/51 Overcur. Always Always 50-3 active
1217 50-3 PICKUP 50/51 Overcur. 1A 1.00 .. 35.00 A; ∞∞A 50-3 Pickup
5A 5.00 .. 175.00 A; ∞∞A
1218 50-3 DELAY 50/51 Overcur. 0.00 .. 60.00 sec; ∞ 0.00 sec 50-3 Time Delay
1219A 50-3 measurem. 50/51 Overcur. Fundamental
True RMS
Instantaneous
Fundamental 50-3 measurement of
1220A 50-2 measurem. 50/51 Overcur. Fundamental
True RMS
Fundamental 50-2 measurement of
1221A 50-1 measurem. 50/51 Overcur. Fundamental
True RMS
Fundamental 50-1 measurement of
Addr. Parameter Function C Setting Options Default Setting Comments