5019 59-1 PICKUP V1 27/59 O/U Volt. 20 .. 150 V 110 V 59-1 Pickup V1
5020 59-2 PICKUP V1 27/59 O/U Volt. 20 .. 150 V 120 V 59-2 Pickup V1
5101 FCT 27 27/59 O/U Volt. OFF
ON
Alarm Only
OFF 27 Undervoltage Protection
5102 27-1 PICKUP 27/59 O/U Volt. 10 .. 210 V 75 V 27-1 Pickup
5103 27-1 PICKUP 27/59 O/U Volt. 10 .. 120 V 45 V 27-1 Pickup
5106 27-1 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec; 1.50 sec 27-1 Time Delay
5110 27-2 PICKUP 27/59 O/U Volt. 10 .. 210 V 70 V 27-2 Pickup
5111 27-2 PICKUP 27/59 O/U Volt. 10 .. 120 V 40 V 27-2 Pickup
5112 27-2 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec; 0.50 sec 27-2 Time Delay
5113A 27-1 DOUT RATIO 27/59 O/U Volt. 1.01 .. 3.00 1.20 27-1 Dropout Ratio
5114A 27-2 DOUT RATIO 27/59 O/U Volt. 1.01 .. 3.00 1.20 27-2 Dropout Ratio
5120A CURRENT SUPERV. 27/59 O/U Volt. OFF
ON
ON Current Supervision
5201 VT BROKEN WIRE Measurem.Superv ON
OFF
OFF VT broken wire supervision
5202 Σ V> Measurem.Superv 1.0 .. 100.0 V 8.0 V Threshold voltage sum
5203 Vph-ph max< Measurem.Superv 1.0 .. 100.0 V 16.0 V Maximum phase to phase
voltage
5204 Vph-ph min< Measurem.Superv 1.0 .. 100.0 V 16.0 V Minimum phase to phase voltage
5205 Vph-ph max-min> Measurem.Superv 10.0 .. 200.0 V 16.0 V Symmetry phase to phase volt-
ages
5206 I min> Measurem.Superv 1A 0.04 .. 1.00 A 0.04 A Minimum line current
5A 0.20 .. 5.00 A 0.20 A
5208 T DELAY ALARM Measurem.Superv 0.00 .. 32.00 sec 1.25 sec Alarm delay time
5301 FUSE FAIL MON. Measurem.Superv OFF
Solid grounded
Coil.gnd./isol.
OFF Fuse Fail Monitor
5302 FUSE FAIL 3Vo Measurem.Superv 10 .. 100 V 30 V Zero Sequence Voltage
5303 FUSE FAIL RESID Measurem.Superv 1A 0.10 .. 1.00 A 0.10 A Residual Current
5A 0.50 .. 5.00 A 0.50 A
5308A FFM Idiff (3ph) Measurem.Superv 1A 0.05 .. 1.00 A 0.10 A Differential Current Threshold
(3phase)
5A 0.25 .. 5.00 A 0.50 A
5310 BLOCK PROT. Measurem.Superv NO
YES
YES Block protection by FFM
5401 FCT 81 O/U 81 O/U Freq. OFF
ON
OFF 81 Over/Under Frequency Pro-
tection
5402 Vmin 81 O/U Freq. 10 .. 150 V 65 V Minimum required voltage for op-
eration
5402 Vmin 81 O/U Freq. 20 .. 150 V 35 V Minimum required voltage for op-
eration
5403 81-1 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 49.50 Hz 81-1 Pickup
5404 81-1 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 59.50 Hz 81-1 Pickup
5405 81-1 DELAY 81 O/U Freq. 0.00 .. 100.00 sec; 60.00 sec 81-1 Time Delay
5406 81-2 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 49.00 Hz 81-2 Pickup
5407 81-2 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 59.00 Hz 81-2 Pickup
5408 81-2 DELAY 81 O/U Freq. 0.00 .. 100.00 sec; 30.00 sec 81-2 Time Delay
5409 81-3 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 47.50 Hz 81-3 Pickup
5410 81-3 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 57.50 Hz 81-3 Pickup
5411 81-3 DELAY 81 O/U Freq. 0.00 .. 100.00 sec; 3.00 sec 81-3 Time delay
5412 81-4 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 51.00 Hz 81-4 Pickup
5413 81-4 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 61.00 Hz 81-4 Pickup
5414 81-4 DELAY 81 O/U Freq. 0.00 .. 100.00 sec; 30.00 sec 81-4 Time delay
5415A DO differential 81 O/U Freq. 0.02 .. 1.00 Hz 0.02 Hz Dropout differential
5421 FCT 81-1 O/U 81 O/U Freq. OFF
ON f>
ON f<
OFF 81-1 Over/Under Frequency Pro-
tection
Addr. Parameter Function C Setting Options Default Setting Comments