Appendix
A.8 Settings
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
467
9003 IP address[2] RTD-Box 0 .. 255 0 IP address[2] of RTD box,
connec. by UDP
9004 IP address[3] RTD-Box 0 .. 255 0 IP address[3] of RTD box,
connec. by UDP
9005 UDP Port RTD-Box 0 .. 65535 5000 UDP service port in the RTD box
9006 IP address[0] RTD-Box 0 .. 255 0 IP address[0] of RTD box,
connec. by UDP
9007 IP address[1] RTD-Box 0 .. 255 0 IP address[1] of RTD box,
connec. by UDP
9008 IP address[2] RTD-Box 0 .. 255 0 IP address[2] of RTD box,
connec. by UDP
9009 IP address[3] RTD-Box 0 .. 255 0 IP address[3] of RTD box,
connec. by UDP
9011A RTD 1 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 1: Temperature Stage 1
Pickup
9014 RTD 1 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 1: Temperature Stage 1
Pickup
9015 RTD 1 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 1: Temperature Stage 2
Pickup
9016 RTD 1 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 1: Temperature Stage 2
Pickup
9021A RTD 2 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 2: Temperature Stage 1
Pickup
9024 RTD 2 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 2: Temperature Stage 1
Pickup
9025 RTD 2 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 2: Temperature Stage 2
Pickup
9026 RTD 2 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 2: Temperature Stage 2
Pickup
9031A RTD 3 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 3: Temperature Stage 1
Pickup
9034 RTD 3 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 3: Temperature Stage 1
Pickup
9035 RTD 3 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 3: Temperature Stage 2
Pickup
9041A RTD 4 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 4: Type
Addr. Parameter Function C Setting Options Default Setting Comments