Settings Menu
Configuration > Data Storage
Parameter Range Default Setting
COM1-RS485 Protocol ASCII, IEC 60870-5-103, MODBUS-
RTU, DNP3, Off
Off
COM1-RS485 Station address 0 to 254 for IEC 60870-5-103
1 to 247 for Modbus RTU
0 to 65534 for DNP3
0
COM1-RS485 Baud rate 75, 110, 150, 300, 600, 1200,
2400, 4800, 9600, 19200, 38400,
57600, 115200, 230400
19200
COM1-RS485 Parity NONE, ODD, EVEN EVEN
COM1-RS485 Mode Local, Remote, Local or Remote Remote
USB Mode Local, Remote, Local or Remote Local
Ethernet Mode Local, Remote, Local or Remote Remote
DNP3 Unsolicited events Disabled, Enabled Disabled
DNP3 Destination address 0 to 65534 0
DNP3 Application timeout 5 to 300 s 10 s
Ethernet Parameters
The Ethernet interface parameters are configured in the Reydisp Manager pc software using the device
Configure Interface tool and can not be configured from the fascia or device settings.
The devices support the Editions 1 and 2 of IEC 61850, and the selection is made in Reydisp Manager when
creating the device. To provide complete compatibility with existing Edition 1 devices, you can use Reydisp
Manager to switch the IEC 61850 server of the device to the Edition 1 mode. The IEC 61850 server then oper-
ates together with Edition 1 clients and exchanges GOOSE messages with Edition 1 devices.
3.7.4
Device Functionality
3.7 Data Communications
126 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019