Logic of the Function
[lo_7SR5_QuickLogic_LogicOfTheFunction, 1, en_US]
Application and Setting Notes
Parameter: En =
Default Setting:
Each logic equation is built up from text representing control characters. Each can be up to 20 characters
long. Allowable characters are:
0, 1, 2, 3, 4, 5, 6, 7, 8, 9
Digit
() Parenthesis
! NOT Function
. AND Function
^ EXCLUSIVE OR Function
+ OR Function
En Equation (number)
Fn Function Key (number)
‘1’ = Key pressed, ‘0’ = Key not pressed
In Binary input (number)
‘1’ = Input energized, ‘0’ = Input de-energized
Ln LED (number)
‘1’ = Input energized, ‘0’ = Input de-energized
3.8.3
3.8.4
Device Functionality
3.8 Quick Logic
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 131
C53000-G7040-C014-1, Edition 11.2019