IEC 61850 Functional Information Mapping
A27PTUV*.Mod
Information
27 Undervoltage Enabled (Function Config) 0 1 1 x x
Inhibit 27-n x 0 1 x x
27-n Enabled 1 1 1 0 x
27-n Operation: Under 1 1 1 x 0
A27PTUV*.Mod.stVal 2 1 2 5 5
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A27PTUV*.Health
Information
Device Healthy 0 1
A27PTUV*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A27PTUV*.Op
Information
27-n Operated 0 1
A27PTUV*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A27PTUV*.Str
Information
27-n Pickup 0 1
A27PTUV*.Str.general 0 1
5.2.6
Protection and Automation Functions
5.2 27 Undervoltage Protection – 3-Phase
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 155
C53000-G7040-C014-1, Edition 11.2019