Functions > Protection > 37 > Gn 37-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Pickup Option Any
All
All
IEC 61850 Functional Information Mapping
A37PTUC*.Mod
Information
37 Undercurrent Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A37PTUC*.Mod 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A37PTUC*.Health
Information
Device Healthy 0 1
A37PTUC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A37PTUC*.Op
Information
Element Operated 0 1
A37PTUC*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
5.5.6
Protection and Automation Functions
5.5 37 Undercurrent Protection – Phase
176 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019