A50GSPTOC*.Op
Information
Element Operated 0 1
A50GSPTOC*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A50GSPTOC*.Str
Information
Element Phase A picked up or 0 1
Element Phase B picked up or 0 1
Element Phase C picked up 0 1
A50GSPTOC*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element picked up and Fwd Direction 0 1 0
Element picked up and Rev Direction 1 0 0
A50GSPTOC*.Str.dirGeneral 2 1 0
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value No-Dir: 0
FWD: 1
REV: 2
Information List
Input/Output Matrix
General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 50GS-n Inhibit 50GS-n Input
E/F off/on Control Y Y Y
50GS-n
Pickup
50GS-n Pickup Output
50GS-n 50GS-n Operated Output Y Y Y
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.14.7
Protection and Automation Functions
5.14 50GS Instantaneous Sensitive Earth Fault – Measured
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 233
C53000-G7040-C014-1, Edition 11.2019