EasyManua.ls Logo

Siemens 7SR51 - Page 247

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element Phase B picked up and Fwd Direction 0 1 0
Element Phase B picked up and Rev Direction 1 0 0
SOTFPTOC*.Str.dirPhsB 2 1 0
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value No-Dir: 0
FWD: 1
REV: 2
Information
Element Phase C picked up 0 1
SOTFPTOC*.Str.phsC 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element Phase C picked up and Fwd Direction 0 1 0
Element Phase C picked up and Rev Direction 1 0 0
SOTFPTOC*.Str.dirPhsC 2 1 0
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value No-Dir: 0
FWD: 1
REV: 2
SOTFGPTOC*.Mod
Information
50SOTFG Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
SOTFGPTOC*.Mod.stVal 5 5 2 1
Protection and Automation Functions
5.16 50SOTF Switch onto Fault
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 247
C53000-G7040-C014-1, Edition 11.2019