Table 5-1 Application of IDMTL Characteristics
OC/EF Curve Characteristic Application
IEC Normal Inverse (NI)
ANSI Moderately Inverse (MI)
Generally applied
IEC Very Inverse (VI)
ANSI Very Inverse (VI)
Used with high‑impedance paths where there is a
significant difference between fault levels at protec-
tion points.
IEC Extreme Inversely (EI)
ANSI Extremely Inverse (EI)
Grading with fuses
IEC Long Time Inverse (LTI) Used to protect transformer earthing resistors having
long withstand times.
Recloser Specific Use when grading with specific recloser.
Reset Delay
The increasing use of plastic insulated cables, both conventionally buried and aerial bundled conductors, have
given rise to the number of flashing intermittent faults on distribution systems. At the fault position, the
plastic melts and temporarily reseals the faulty cable for a short time after which the insulation fails again. The
same phenomenon has occurred in compound‑filled joint boxes or on “clashing” overhead line conductors.
The repeating process of the fault can cause electromechanical disc relays to “ratchet” up and eventually trip
the faulty circuit if the reset time of the relay is longer than the time between successive faults.
To mimic an electromechanical relay the relay can be user programmed for an ANSI Decaying characteristic
when an ANSI Operate characteristic is applied. Alternatively a DTL reset (0 to 60 seconds) can be used with
other operate characteristics.
For protection of cable feeders, it is recommended that a 60 second DTL reset be used.
On overhead line networks, particularly where reclosers are incorporated in the protected system, instanta-
neous resetting is desirable to ensure that, on multiple shot reclosing schemes, correct grading between the
source relays and the relays associated with the reclosers is maintained.
[dw_7SR5_function51drawing, 1, en_US]
Figure 5-26 Needs a title
Protection and Automation Functions
5.17 51 Time-Delayed Overcurrent – Phase
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 261
C53000-G7040-C014-1, Edition 11.2019