EasyManua.ls Logo

Siemens 7SR51 - IEC 61850 Functional Information Mapping

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions > Protection > 51GS > Gn 51GS-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
9
Off
Inhibit
Non-Dir
Off
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A51GSPTOC*.Mod
Information
51GS Sensitive EF Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A51GSPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A51GSPTOC*.Health
Information
Device Healthy 0 1
A51GSPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A51GSPTOC*.Op
Information
Element Operated 0 1
A51GSPTOC*.Op.general 0 1
5.19.6
Protection and Automation Functions
5.19 51GS Time-Delayed Sensitive Earth Fault – Measured
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 283
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals