Functions > Protection > 51GS > Gn 51GS-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
9
Off
Inhibit
Non-Dir
Off
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A51GSPTOC*.Mod
Information
51GS Sensitive EF Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A51GSPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A51GSPTOC*.Health
Information
Device Healthy 0 1
A51GSPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A51GSPTOC*.Op
Information
Element Operated 0 1
A51GSPTOC*.Op.general 0 1