Siemens 7SR51 - IEC 61850 Functional Information Mapping

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions > Protection > 51N > Gn 51N-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Time Mult (IEC/ANSI) 0.01 to 1.6, Δ 0.01
1.6 to 5, Δ 0.1
5 to 100, Δ 1
1
Delay (DTL) 0 to 20 s Δ 0.01 s 5 s
Min Operate Time 0 to 20 s Δ 0.01 s 0 s
Follower DTL 0 to 20 s Δ 0.01 s 0 s
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
10
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit No
Yes
No
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A51NPTOC*.Mod
Information
51N Earth Fault Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A51NPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A51NPTOC*.Health
Information
Device Healthy 0 1
A51NPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
5.20.6
Protection and Automation Functions
5.20 51N Time-Delayed Earth Fault – Calculated
292 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019