Logic of the Function
[lo_7SR5_55logicdiagram, 1, en_US]
Figure 5-33
Logic Diagram: 55 Power Factor
Application and Setting Notes
Parameter: Operation
Default setting: Under
Each element can be individually set to indicate operation when the power factor is above or below the
set threshold. Normal system operating conditions generally have a power factor approaching unity and
an Under-PF element will operate to indicate unwanted conditions. An Over-PF element is useful to
provide an operated indication during normal healthy conditions.
5.21.3
5.21.4
Protection and Automation Functions
5.21 55 Power Factor