EasyManua.ls Logo

Siemens 7SR51 - Page 298

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter: 55-n UC Guard
Default setting: Enabled
This can be used to block element operation if the current is below the setting in all 3 phases (?). This is
used to avoid nuisance operations at very low levels of current.
Parameter: UC Guard Setting
Default setting: 0.2 x I
n
(0.2 ⋅ I
rated
)
This defines the minimum current required for the element to operate. This should be set to a level below
which the power factor should not be considered as significant or cannot be measured accurately.
Parameter: VTS Inhibit
Default setting: No
The 55-n element can be set to be automatically inhibited when a voltage has been identified as invalid
by the VTS element.
Settings Example
An output is required when any phase load has a power factor below 0.8 lagging for more than 10 seconds.
[dw_7SR5_function55SettingsExample, 1, en_US]
Functions > Protection > 55
Element Enabled
Operation Under
1Ph/3Ph Power 1Ph
Dir. Control Lag
Setting 0.8
Delay 10 s
UC Guard Enabled
UC Guard Setting 0.1 ⋅ I
rated
Protection and Automation Functions
5.21 55 Power Factor
298 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals