Element Phase C picked up 0 1
A59PTOV*.Str.phsC 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information List
Input/Output Matrix General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 59-n Inhibit 59-n Input
59-n 59-n Operated Output Y Y Y
59 PhA 59-n PhA Operated Output Y Y Y
59 PhB 59-n PhB Operated Output Y Y Y
59 PhC 59-n PhC Operated Output Y Y Y
59-n
Pickup
59-n Pickup Output
59-n PhA Pickup Output
59-n PhB Pickup Output
59-n PhC Pickup Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.